Which valves can DCL electric actuators drive?

Which valves can DCL electric actuators drive?

       DCL electric actuators are mainly used to actuate butterfly valves with a diameter of less than 600 mm, ball valves with a diameter of less than 350 mm, as well as ventilation valves and damper flaps with a diameter of less than 1200 mm. In addition to this, some interesting drive applications deserve our attention. For example, rotating solar panels to catch the light, driving blinds for natural ventilation, driving flaps for specific scenarios by means of a turning arm, and so on.

Actuated Butterfly Valve

      DCL electric actuator can drive butterfly valves in the range of DN50~DN600. Under normal working condition, the pipeline pressure is not more than 1.0MPa. when the pipeline pressure is more than 1.0MPa, you need to choose the right model according to the torque parameter of the valve. You can Contact techniciansto determine if the motorized actuator is properly sized.

蝶阀(压力≤PN1.0MPa)额定扭矩(Nm)General Series ActuatorExplosion-proof series actuator
DN50~6550DCL-05DCL-Ex05
DN80~100100DCL-10DCL-Ex10
DN125~150200DCL-20DCL-Ex20
DN200400DCL-40DCL-Ex40
DN250600DCL-60DCL-Ex60
DN3001000DCL-100
DN350~4001600DCL-160
DN450~6002500DCL-250

Actuated Ball Valves

      DCL electric actuators can drive ball valves in the range of DN40~DN350. Under normal working condition, the pipeline pressure is not more than 1.0MPa. When the pipeline pressure is more than 1.0MPa, it is necessary to choose the appropriate model according to the torque parameter of the valve. You can Contact techniciansto determine if the motorized actuator is properly sized.

球阀(压力≤PN1.6MPa)额定扭矩(Nm)General Series ActuatorExplosion-proof series actuator
DN4050DCL-05DCL-Ex05
DN50~65100DCL-10DCL-Ex10
DN80~100200DCL-20DCL-Ex20
DN125400DCL-40DCL-Ex40
DN150600DCL-60DCL-Ex60
DN2001000DCL-100
DN2501600DCL-160
DN300~3502500DCL-250

Actuated dampers and damper flaps

      DCL electric actuators can drive dampers in the range of DN50~DN1200. Under normal working condition, the pipeline pressure is not more than 0.1MPa. When the pipeline pressure is more than 0.1MPa, it is necessary to choose the appropriate model according to the torque parameter of the valve. You can Contact techniciansto determine if the motorized actuator is properly sized.

通风阀(≤PN0.1MPa)额定扭矩(Nm)General Series ActuatorExplosion-proof series actuator
DN50~8050DCL-05DCL-Ex05
DN100~200100DCL-10DCL-Ex10
DN250~300200DCL-20DCL-Ex20
DN350~450400DCL-40DCL-Ex40
DN500~600600DCL-60DCL-Ex60
DN700~8001000DCL-100
DN9001600DCL-160
DN1000~12002500DCL-250

      The passage diameter, pressure and friction coefficient of the duct have an influence on the required drive torque of the damper. The torque of the damper actuator can be determined by referring to the following table:

通径(mm)压力(bar)摩擦系数力矩(kg-m)
200100.1523.15
200100.2527.86
250100.135.01
250100.1539.92
250100.2549.75
300100.159.51
300100.1567.47
300100.2583.38
350100.181.19
350100.1592.03
350100.25113.69
400100.1109.49
400100.15120.49
400100.25156.65
450100.1149.8
450100.15170.83
450100.25218.58
500100.15266.22
500100.25335
550100.1287.24
550100.15331.82
550100.25420.98
600100.1355.09
600100.15406.52
600100.25519.71
650100.1449.33
650100.15503.95
650100.25631.98
700100.1586.7
700100.15678.17
700100.25861.11
800100.1819.51
800100.15940.67
800100.251192.31
900100.11186.13
900100.151327.81
900100.251611.15
100060.1996.28
100060.151095.75
1000100.11603.41
1000100.151763.11
1000100.252150.94
110060.11396.38
110060.151574.71
110060.251931.35
1100100.12126.78
1100100.152366.02
1100100.252875.61
120060.11703.89
120060.151915.73
120060.252357.15
1200100.12753.18
1200100.153059.8
1200100.253673.03
130060.12151.23
130060.152326.25
130060.252836.89
1300100.13543.27
1300100.153954.52
1300100.254777.03
140060.12670.64
140060.152881.14
140060.253373.82
1400100.14441.51
1400100.154963.18
1400100.256006.53
150060.13383.88
150060.153781.8
150060.254577.62
1500100.15548.41
1500100.156232.82
1500100.257689.31
160060.13986.5
160060.154432.28
1600100.16785.63
1600100.157642.21
1600100.259379.74
180060.15676.09
180060.156123.48
1800100.2513140.31
200060.18139.04
200060.159176.55
200060.2511251.6
2000100.113070.69
2000100.1514652.43
2000100.2517815.93
220060.110437.6
220060.1511474.04
220060.2514098.96
2200100.117308.75
2200100.2523492.16
240060.113454.44
240060.1514514.93
240060.2517378.15
2400100.122375.98
2400100.1525004.03
2400100.2530260.3
260060.117040.2
260060.1519032.71
260060.2523017.73
2600100.128346.48
2600100.1531636.21
2600100.2538216.28
280060.121124.58
280060.1522765.63
280060.2527572.18
2800100.135293.63
2800100.1539347.76
2800100.2547456.04
300060.125863.96
300060.1527728.1
300060.2532693.85
3000100.143292.29
3000100.1548220.04
3000100.2558075.54

Driving other types of valves

      Of course, DCL electric actuators can also drive other types of partially rotating valves such as three-way valves. You can Contact technicians, select the appropriate type and model of electric actuator.

Determine specific valve drive parameters

      For specific fluid control conditions, you need to follow the fluid pressure, media type, control mode and other factors, clear the final valve drive parameters to ensure that the selection of electric actuators to meet the requirements of the site conditions. The following parameters should be determined before the actuator finalization:

  • 0~90°
  • 0~360°

            Nm/    S

  • switching type
  • regulating type
  • Continuously adjustable
  • DC24V
  • AC24V
  • AC110V
  • AC220V
  • AC380V
  • 4-20mA
  • 2-10V
  • direct drive
  • Modbus
  • Fondation Fieldbus
  • HART
  • Profinet
  • Profibus
  • DeviceNet
  • Pakscan
  • Over-torque protection
  • Power failure reset
  • Self-heating dehumidification
  • Valve monitoring/diagnostics
  • waterproofing
  • underwater
  • flameproof
  • Power failure reset
  • functional safety

Parameter range of DCL electric actuators

Adaptive Valve

Partial rotation
damper
0~90° | 0~360°

Torque/Time

18~2500Nm
2S~75S

Type of control

switching type
regulating type
Continuously adjustable

Supply Voltage

DC24V
AC24V
AC110V
AC220V
AC380V

Input/Output Signal

4~20mA
0~10V
Level | Contacts
Modbus-RTU | CAN | Ethernet

optional

Over-torque protection
Power failure reset
Self-heating dehumidification
self-diagnosis

Driving other devices

Driving light chasing rotation of solar PV panels

Drive blinds

Driving of the flap by means of a swing arm